← All Maps

Schneider Electric PowerLogic PM810

Power Meter

Addressing: Modicon
Registers: 959
Address Description FC Count Data Type Byte Order Access Units Scale Range Category Vendor Notes
620 Duplicate IP Address Check Register 2 OCTET ABCD R/W Communication Range: IP Address Format. Volatile register used for duplicate IP detection. The PM8 writes the requested IP to these registers and signals the ECC to perform a Duplicate IP Check on it.
622 IP Address 2 OCTET ABCD R/CW Communication Range: IP Address Format. First octet must not be 0x00. Duplicate IP check must be made before writing this value.
624 IP Subnet Mask 2 OCTET ABCD R/CW Communication Range: IP Address Format. Last octet can not be set to 254. Network part of the mask must be all 1s and device part must be all 0s. example: 255.255.255.0 is good 255.253.255.0 is invalid.
626 IP Router Address 2 OCTET ABCD R/CW Communication Range: IP Address Format. No checking is done on the router address.
629 Baud Rate 1 INT16U N/A R/CW 5=2400;6=4800;7=9600;8=19200 (Default);9=38400
630 Parity 1 INT16U N/A R/CW 0=None;2=Even (Default)
631 Wire Mode 1 INT16U N/A R/CW 1=2-Wire (Default);2=4-Wire
632 Port Protocol Mode 1 INT16U N/A R/CW 0=Device Selectable (Auto)(Default);1=Modbus ASCII
633 PM8ECC Reset Counter 1 INT16U N/A R/W Communication Range: 0-65535. This register is incremented each time the PM8ECC starts up.
634 Frame Type 1 INT16U N/A R/CW 0=Ethernet II (Default);1=802.3 SNAP
1100 Current Phase A 1 INT16U N/A R/O Amps/Scale A
1101 Current Phase B 1 INT16U N/A R/O Amps/Scale A
1102 Current Phase C 1 INT16U N/A R/O Amps/Scale A
1103 Current Neutral 1 INT16U N/A R/O Amps/Scale B
1104 Current Ground 1 INT16U N/A R/O Amps/Scale B
1105 Current 3-Phase Average 1 INT16U N/A R/O Amps/Scale A
1107 Current Unbalance Phase A 1 INT16U N/A R/O % 0.10%
1108 Current Unbalance Phase B 1 INT16U N/A R/O % 0.10%
1109 Current Unbalance Phase C 1 INT16U N/A R/O % 0.10%
1110 Current Unbalance Max 1 INT16U N/A R/O % 0.10%
1120 Voltage A-B 1 INT16U N/A R/O Volts/Scale D
1121 Voltage B-C 1 INT16U N/A R/O Volts/Scale D
1122 Voltage C-A 1 INT16U N/A R/O Volts/Scale D
1123 Voltage L-L Average 1 INT16U N/A R/O Volts/Scale D
1124 Voltage A-N 1 INT16U N/A R/O Volts/Scale D
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R

934 more registers available