← All Maps

ABB Energy Efficency M4M

Digital Network AnalyzersFirmware v1.3O

TCP Port: 502
Registers: 1364
Address Description FC Count Data Type Byte Order Access Units Scale Range Category Vendor Notes
5000 Active energy - import 3 4 INT64U ABCD R/O kWh 0.01 Data Reading - Energy (total) Applicable models: M4M 20 (all versions); M4M 30 (all versions)
20484 Active energy - export 3 4 INT64U ABCD R/O kWh 0.01 Data Reading - Energy (total) Applicable models: M4M 20 (all versions); M4M 30 (all versions)
20488 Active energy - net 3 4 INT64S ABCD R/O kWh 0.01 Data Reading - Energy (total) Applicable models: M4M 20 (all versions); M4M 30 (all versions)
20492 Reactive energy - import 3 4 INT64U ABCD R/O kvarh 0.01 Data Reading - Energy (total) Applicable models: M4M 20 (all versions); M4M 30 (all versions)
20496 Reactive energy - export 3 4 INT64U ABCD R/O kvarh 0.01 Data Reading - Energy (total) Applicable models: M4M 20 (all versions); M4M 30 (all versions)
20500 Reactive energy - net 3 4 INT64S ABCD R/O kvarh 0.01 Data Reading - Energy (total) Applicable models: M4M 20 (all versions); M4M 30 (all versions)
20504 Apparent energy - import 3 4 INT64U ABCD R/O kVA 0.01 Data Reading - Energy (total) Applicable models: M4M 20 (all versions); M4M 30 (all versions)
20508 Apparent energy - export 3 4 INT64U ABCD R/O kVA 0.01 Data Reading - Energy (total) Applicable models: M4M 20 (all versions); M4M 30 (all versions)
20512 Apparent energy - net 3 4 INT64S ABCD R/O kVA 0.01 Data Reading - Energy (total) Applicable models: M4M 20 (all versions); M4M 30 (all versions)
20516 Active energy - import [Details: CO2 conversion factor] 3 4 INT64U ABCD R/O kg / kWh 0.001 Data Reading - Energy Conversion Applicable models: M4M 20 (all versions); M4M 30 (all versions)
20532 Active energy - import [Details: Currency conversion factor] 3 4 INT64U ABCD R/O Currency / kWh 0.001 Data Reading - Energy Conversion Applicable models: M4M 20 (all versions); M4M 30 (all versions)
20848 Active energy - import (Tariffs) [Details: Tariff from 1 to 6] - Item 1 of 6 3 4 INT64U ABCD R/O kWh 0.01 Data Reading - Energy (per tariff) Applicable models: M4M 30 (all versions)
20852 Active energy - import (Tariffs) [Details: Tariff from 1 to 6] - Item 2 of 6 3 4 INT64U ABCD R/O kWh 0.01 Data Reading - Energy (per tariff) Applicable models: M4M 30 (all versions)
20856 Active energy - import (Tariffs) [Details: Tariff from 1 to 6] - Item 3 of 6 3 4 INT64U ABCD R/O kWh 0.01 Data Reading - Energy (per tariff) Applicable models: M4M 30 (all versions)
20860 Active energy - import (Tariffs) [Details: Tariff from 1 to 6] - Item 4 of 6 3 4 INT64U ABCD R/O kWh 0.01 Data Reading - Energy (per tariff) Applicable models: M4M 30 (all versions)
20864 Active energy - import (Tariffs) [Details: Tariff from 1 to 6] - Item 5 of 6 3 4 INT64U ABCD R/O kWh 0.01 Data Reading - Energy (per tariff) Applicable models: M4M 30 (all versions)
20868 Active energy - import (Tariffs) [Details: Tariff from 1 to 6] - Item 6 of 6 3 4 INT64U ABCD R/O kWh 0.01 Data Reading - Energy (per tariff) Applicable models: M4M 30 (all versions)
20880 Active energy - export (Tariffs) [Details: Tariff from 1 to 6] - Item 1 of 6 3 4 INT64U ABCD R/O kWh 0.01 Data Reading - Energy (per tariff) Applicable models: M4M 30 (all versions)
20884 Active energy - export (Tariffs) [Details: Tariff from 1 to 6] - Item 2 of 6 3 4 INT64U ABCD R/O kWh 0.01 Data Reading - Energy (per tariff) Applicable models: M4M 30 (all versions)
20888 Active energy - export (Tariffs) [Details: Tariff from 1 to 6] - Item 3 of 6 3 4 INT64U ABCD R/O kWh 0.01 Data Reading - Energy (per tariff) Applicable models: M4M 30 (all versions)
20892 Active energy - export (Tariffs) [Details: Tariff from 1 to 6] - Item 4 of 6 3 4 INT64U ABCD R/O kWh 0.01 Data Reading - Energy (per tariff) Applicable models: M4M 30 (all versions)
20896 Active energy - export (Tariffs) [Details: Tariff from 1 to 6] - Item 5 of 6 3 4 INT64U ABCD R/O kWh 0.01 Data Reading - Energy (per tariff) Applicable models: M4M 30 (all versions)
20900 Active energy - export (Tariffs) [Details: Tariff from 1 to 6] - Item 6 of 6 3 4 INT64U ABCD R/O kWh 0.01 Data Reading - Energy (per tariff) Applicable models: M4M 30 (all versions)
20912 Reactive energy - import (Tariffs) [Details: Tariff from 1 to 6] - Item 1 of 6 3 4 INT64U ABCD R/O kvarh 0.01 Data Reading - Energy (per tariff) Applicable models: M4M 30 (all versions)
20916 Reactive energy - import (Tariffs) [Details: Tariff from 1 to 6] - Item 2 of 6 3 4 INT64U ABCD R/O kvarh 0.01 Data Reading - Energy (per tariff) Applicable models: M4M 30 (all versions)
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R
00000 Register description hidden 03 1 UInt16 ABCD R

1339 more registers available